繞組直流電阻測量
1) 對(dui)電(dian)壓互感器一次繞組,宜采用單臂電(dian)橋進(jin)行測量;
2) 對電(dian)(dian)壓互感器(qi)的二(er)(er)次(ci)繞(rao)(rao)組(zu)以及電(dian)(dian)流互感器(qi)的一(yi)次(ci)或二(er)(er)次(ci)繞(rao)(rao)組(zu),宜采用雙(shuang)臂電(dian)(dian)橋進行測(ce)(ce)量,如果二(er)(er)次(ci)繞(rao)(rao)組(zu)直流電(dian)(dian)阻超過10Ω,應采用單臂電(dian)(dian)橋測(ce)(ce)量;
3) 也可采用直(zhi)流(liu)(liu)電阻測試儀(yi)進(jin)行測量(liang)(liang),但應注意測試電流(liu)(liu)不(bu)宜超過(guo)線圈額定(ding)電流(liu)(liu)的20%,以免線圈發熱直(zhi)流(liu)(liu)電阻增加,影響測量(liang)(liang)的準(zhun)確(que)度(du)。
4) 試驗接線:
將(jiang)被(bei)試(shi)繞(rao)組首尾端分別接入電(dian)橋,非(fei)被(bei)試(shi)繞(rao)組懸空,采用雙臂(bei)電(dian)橋 (或數字式直流電(dian)阻測試(shi)儀) 時,電(dian)流端子(zi)應(ying)在電(dian)壓(ya)端子(zi)的外側;
5)換接線時(shi)應斷(duan)開(kai)電(dian)(dian)橋的電(dian)(dian)源(yuan),并對(dui)被試繞組(zu)短路充(chong)分(fen)放電(dian)(dian)后才能拆(chai)開(kai)測量端(duan)(duan)子(zi),如(ru)果放電(dian)(dian)不(bu)充(chong)分(fen)而強行斷(duan)開(kai)測量端(duan)(duan)子(zi),容(rong)易造成(cheng)過電(dian)(dian)壓而損壞(huai)線圈的主(zhu)絕緣,一般數(shu)字式直流電(dian)(dian)阻測量裝置都有(you)自動放電(dian)(dian)和警(jing)示功能。
測(ce)量電(dian)(dian)(dian)容式電(dian)(dian)(dian)壓(ya)互感器(qi)(qi)中間(jian)變(bian)壓(ya)器(qi)(qi)二次繞組直流電(dian)(dian)(dian)阻時,應(ying)拆(chai)開(kai)一次繞組與(yu)分(fen)壓(ya)電(dian)(dian)(dian)容器(qi)(qi)的(de)連(lian)接(jie)和二次繞組的(de)外部(bu)連(lian)接(jie)線,當中間(jian)變(bian)壓(ya)器(qi)(qi)一次繞組與(yu)分(fen)壓(ya)電(dian)(dian)(dian)容器(qi)(qi)在內(nei)部(bu)連(lian)接(jie)而無法分(fen)開(kai)時,可不測(ce)量次繞組的(de)直流電(dian)(dian)(dian)阻。
試驗要點:
測量電流(liu)不宜(yi)大于按繞組額定負(fu)載計算所得的輸(shu)出電流(liu)的50%。
當線圈匝數(shu)較多而電感較大(da)時(shi),應(ying)待(dai)儀器顯示的(de)數(shu)據穩定(ding)后方(fang)可(ke)讀取數(shu)據,測(ce)量(liang)結束后應(ying)待(dai)直(zhi)流電阻測(ce)試(shi)儀器充分(fen)放電后方(fang)可(ke)斷開(kai)測(ce)量(liang)回路。
記錄試(shi)驗時環境溫度(du)和空氣(qi)相對濕度(du)。
直流電阻測量值應換算到同(tong)一溫度下(xia)進行比(bi)較。
結果判斷
與歷次試(shi)驗(yan)結(jie)果和同類設備(bei)的(de)試(shi)驗(yan)結(jie)果相比無顯著差別(bie)。
電話(hua):86-021-56473713 傳真(zhen):86-021-56473709
地址:上海市(shi)閘(zha)北區江楊南路466弄
郵編(bian):
GoogleSiteMap ICP備案號: